Warning issued over damaged switchboard wiring


Thursday, 01 October, 2020


Warning issued over damaged switchboard wiring

The Queensland Electrical Safety Office has conducted an investigation into several incidents where switchboard wiring had been damaged.

Damage resulted in active conductors shorting to either earthed switchboard enclosures or neutral bars inside the switchboard.

According to an alert from the Electrical Safety Office, when a fault occurs between an active conductor and earth or neutral within a switchboard, the fault current can cause an arc flash which can injure workers and damage property. The switchboard and installation earthing system will be live during the fault, creating the risk of electric shock to the person working on the switchboard and people nearby.

Three common mistakes were identified as contributing factors to these incidents.

  1. Wiring on hinged meter panels was pushed onto uncovered neutral links installed behind the hinged meter panel when it was closed (as there is often very little room between them in modern switchboards), resulting in cable damage and a short circuit.
  2. Wiring was not appropriately secured to prevent cables contacting metal edges near the meter panel hinge points. Cables pushed against the metal edges were damaged, resulting in a short circuit to the switchboard enclosure.
  3. Wiring was not suitably fixed at the hinged panel and the switchboard, resulting in movement at terminals of electrical equipment and energised cables being dislodged from the terminal.
     

The Electrical Safety Office said that every switchboard is different, but electrical workers and contractors must ensure that switchboard wiring is electrically safe when installed. This includes fixing cables so they don’t suffer damage, cause pressure on electrical equipment, or cause stress on terminals when the panel is moved.

Image credit: ©stock.adobe.com/au/romaset

Related News

The lockdown effect: energy consumption shift revealed

Energy Networks Australia has been mapping the impact of COVID-19 restrictions on energy...

Calls for mandatory safety switches after shock incident

Properly installed safety switches could have prevented almost all recent electric shock...

$35K fine issued after excavator hits powerlines

A conviction and a $35,000 fine have been handed down to a Victorian quarry, after a safety...


  • All content Copyright © 2020 Westwick-Farrow Pty Ltd