Guidelines for electrical inspection and verification testing of flood-affected properties

Tuesday, 18 January, 2011

Energy Safe Victoria is advising electricians and registered electrical contractors how to perform electrical inspections and/or repair works to properties affected by floodwater to ensure these activities are performed in a safe manner.

The recent floods may have caused the presence of water and other foreign external influences to affect premises and result in an unsafe electrical situation. Potential risks include poor insulation resistance, earth leakage and short circuits.

Energy Safe Victoria requires all electricians and registered electrical contractors to carry out work in a safe manner including the performance of a safe approach. This would include:

  • A check of testing equipment to ensure it is functioning correctly;
  • Ensuring appropriate safety apparel is being worn and the work environment is suitable to perform the work safely;
  • A test to prove any exposed conductive parts and parts that would be live in-service ‘de-energised’;
  • A check for isolation of supply (distributors);
  • A check for isolation of supply (alternate, eg, generator/solar); and
  • A re-check of testing equipment to ensure it is still functioning correctly prior to touching parts of the installation.

A visual inspection must be carried out before or in association with mandatory testing before the electrical installation is ready to be placed in service including general condition of the electrical equipment, eg, signs of damage that could impair safe operation, signs of ingress of water to electrical equipment.

Where water has entered electrical equipment, these parts should be replaced or disconnected prior to re-energisation of the electrical installation.

Mandatory testing in accordance with AS/NZS 3000:2007 Amt 1

The following mandatory tests shall be carried out on low-voltage electrical installations prior to them being placed in service:

  • Continuity of the earthing system (earth resistance of the main, protective earthing and bonding conductors);
  • Insulation resistance (of all fixed wiring and appliances to be connected);
  • Polarity;
  • Correct circuit connections;
  • Verification of impedance required for automatic disconnection of supply (earth fault-loop impedance); and
  • Operation of RCDs (if supply is available).

Certificates of Electrical Safety

  • In circumstances where the distribution company has isolated supply to the individual installation, a Certificate of Electrical Safety is required to be completed certifying the electrical installation is safe to be reconnected to supply by the distribution company.
  • In circumstances where the installation has undergone any associated repairs, a Certificate of Electrical Safety is required to be completed.
  • Upon application, Energy Safe Victoria will issue replacement Certificate(s) of Electrical Safety to Electricians and Registered Electrical Contractors where they have performed electrical repair work to premises affected by floodwater, for no profit or gain.
Related News

Bringing geospatial tools to infrastructure planning

Bentley Systems has joined forces with Google to enhance the way infrastructure is designed,...

Funding boost to transition heavy vehicles to electric

ARENA has made $100 million in funding available under its Driving the Nation program to support...

MEA protests terrace housing red tape

A recent determination by Energy Queensland Limited will impose an extra measure when connecting...


  • All content Copyright © 2024 Westwick-Farrow Pty Ltd